- Home
- Thermostats
- 11100.0-01 KT0 111 DIN Rail Enclosure Thermostat Heating -10 to 50°C
Product Description
-
- Compact design
- Wide adjustment range
- Color coded temperature dials
- DIN rail mounted
KTO 011 Thermostat NC (normally closed)
Thermostat closes on temperature rise - for regulating heaters or for switching signal devices. Comes with red temperature dial.DOWNLOAD OPERATING INSTRUCTIONS
Switch temperature difference 12.6°F ± 7°F tolerance (7°K ± 4°K) Sensor element thermostatic bimetal Contact type snap-action contact Service life > 100,000 cycles Max. Switching capacity 250VAC, 10A resistive / 2A inductive 120VAC, 15A resistive / 2A inductive DC 30W (24-72Vdc) Max. inrush current 16A VAC for 10 seconds Connection 2 Push-In clamps rigid wire 2.5 mm² (AWG 14) stranded wire1 1.5 mm² (AWG 16)
Mounting molded plastic clip for 35mm DIN rail, EN60715 Housing plastic according to UL94 V-0, light grey Dimensions 2.4 x 1.3 x 1.6" (60 x 33 x 41 mm) Weight approx. 1.4 oz (40g) Mounting position vertical Operating / Storage temperature -49 to +176°F (-45 to +80°C) Operating / Storage humidity max. 90 % RH (non-condensing) Protection type IP20 / II Setting range Part No. (NC) Part No.(NO) Approvals +32 to 140°F 11100.9-00 11101.9-00 VDE + UL File No. E164102 CSA EAC 0 to +60°C 11100.0-00 11101.0-00 VDE + UL File No. E164102 CSA EAC
-10 to +50°C 11100.0-01 11101.0-01 VDE + UL File No. E164102 EAC +14 to +122°F 11100.9-01 11101.9-01 VDE + UL File No. E164102 CSA EAC +10 to +70°C N/A 01149.9-00 VDE + UL File No. E164102 EAC -15 to +45°C 01157.0-00 01156.0-00 VDE + UL File No. E164102 EAC +20 to +80°C 11100.0-02 11101.0-02 VDE + UL File No. E164102 CSA EAC