- Home
- Thermostats
- 01220.0-00 MFR012 Enclosure Humidity Control 35 to 95 RH 250 VAC
Product Description
- Efficient condensation control
- Adjustable relative humidity range
- High switching capacity
- DIN rail mountable
The MFR 012 electromechanical hygrostat is designed to control the relative humidity inside enclosures. When connected to an enclosure heater (dehumidifier), it will energize the heater at the humidity set point in order to raise the dew point. This helps prevent damage and malfunction of electronic components caused by condensation and corrosion.¹
The MFR 012 can also be used to control cooling fans, warning lights or other devices.
Switching difference | 4% RH (± 3% tolerance) - at 50% RH |
Permissible air velocity | 50 ft/sec (15m/s) |
Contact type | SPDT / change-over contact |
Service life | > 50,000 cycles |
Min. Switching capacity | 100mA @ 20VAC/DC |
Max. Switching capacity | 5A resistive @ 250VAC |
DC 20W | |
Connection | 3-pole terminal, clamping torque 0.5Nm max.: solid wire - AWG 14 max. (2.5mm²) stranded wire (with wire end ferrule) - AWG 16 max. (1.5mm²) |
Housing | plastic, UL 94V-0, light grey |
Mounting | molded plastic clip for 35mm DIN rail, EN 60 715 |
Mounting position | vertical |
Operating/Storage temperature | +32 to +140°F (0 to +60°C) / -40 to +140°F (-40 to +60°C) |
Operating/Storage humidity | max. 95% RH (non-condensing) |
Dimensions | 2.64 x 1.97 x 1.5” (67 x 50 x 38mm) |
Weight | approx. 2 oz. (60g) |
Protection type | IP20 |
Approvals | UL File No. E164102 |
¹) The critical relative humidity level for most components is 65%. Above 65% RH, condensation can form and cause malfunctions of electronic equipment. Long term, this can lead to corrosion and permanent damage of electronic components and systems.
Part. No. | Setting range |
01220.0-00 | 35 to 95% RH |