Product Description
- NC / NO or NO / NO in one unit
- TSeparate Adjustable temperatures
- Color Coded Temperature Dials
- DIN Rail Mount
The ZR 011 houses two separate thermostats, allowing the independent control of heating and cooling or other equipment.
Thermostat NC (normally closed):
Thermostat opens at temperature rise - for regulating heaters or for switching signal devices. Comes with red temperature dial.
Thermostat NO (normally open):
Thermostat closes at temperature rise - for regulating filter fans and heat exchangers or for switching signal devices. Comes with blue temperature dial.
Switch temperature difference | 7K (± 4K tolerance) |
Sensor element | thermostatic bimetal |
Contact type | snap-action contact |
Service life | > 100 000 cycles |
Max. switching capacity | 250VAC, 10 (2) A |
120VAC, 15 (2) A | |
DC 30W | |
Connection | 4-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm², stranded wire (with wire end ferrule) 1.5mm² |
Mounting | clip for 35mm DIN rail, EN60715 |
Casing | plastic according to UL94 V-0. light grey |
Dimensions | 67 x 50 x 46mm |
Weight | approx. 90g |
Fitting position | variable |
Operating/Storage temperature | -45 to +80°C (-49 to +176°F) |
Operating / Storage humidity | max. 90 % RH (non-condensing) |
Protection type | IP20 |
Approvals | UL File No. E164102 |
Art. No. | Setting range | Setting range | Setting range | Setting range |
01172.0-00 | contact breaker, normally closed | 0 to +60°C | contact maker, normally open | 0 to +60°C |
01172.0-01 | contact breaker, normally closed | +32 to +140°F | contact maker, normally open | +32 to +140°F |
01175.0-00 | contact breaker, normally closed | -10 to +50°C | contact maker, normally open | +20 to +80°C |
01175.0-01 | contact breaker, normally closed | +14 to +122°F | contact maker, normally open | +68 to +176 °F |
01176.0-00* | contact maker, normally open | 0 to +60°C | contact maker, normally open | 0 to +60°C |
01176.0-01* | contact maker, normally open | +32 to +140°F | contact maker, normally open | +32 to +140°F |
*For regulating heat exchangers and fans (e.g LE 019) and as an alarm contact for monitoring the interior temperature of electronic enclosures. |