- Home
- Thermostats
- 01163.0-02 FTD011 Enclosure Tamper Proof Dual Thermostat Preset 41F NC & 95F NO
Product Description
- NC / NO or NO / NO in one unit
- Fixed set points
- Color coded modules
- DIN rail mountable
Two thermostats in one housing: Heaters and cooling equipment can be switched independently from each other with a temperature offset as opposed to the usual SPDT/change-over contact.
Tamperproof (Pre-set) Thermostat - NC Opens on temperature rise (red module housing) - for regulating heaters or for switching signal devices when temperature has fallen below the minimum value.
Tamperproof (Pre-set) Thermostat - NO Closes on temperature rise (blue module housing) - for regulating filter fans, heat exchangers, cooling devices or for switching signal devices when temperature limit has been exceeded.
Sensor element | thermostatic bimetal |
Contact type | snap-action contact |
Service life | > 100,000 cycles |
Max. switching capacity | 240V AC, 5A resistive / 1.6A inductive |
120V AC, 10A resistive / 2A inductive | |
DC 30W | |
Max. inrush current | AC 16A for 10 seconds |
Connection | 4-pole terminal, clamping torque 0.8Nm max. solid wire 14 awg max. (2.5mm²) / stranded wire (w/wire end ferrule) 16 awg max. (1.5mm²) |
Housing | plastic according to UL94 V-0, light grey |
Mounting | molded plastic clip for 35mm DIN rail, EN 60715 |
Mounting position | vertical |
Operating/Storage temperature | -40 to +176°F (-40 to + 80°C) / -49 to +176°F (-45 to + 80°C) |
Operating / Storage humidity | max. 90 % RH (non-condensing) |
Dimensions | 1.8x2.5x1.3" (47 x 63 x 33mm) |
Weight | approx. 14.1 oz (40g) |
Protection type | IP20 |
Approvals | cUL (UL File No. E164102), VDE, EAC |
Part No. | Switch-off temperature (NC) Contact | Switch-on temperature (NC) Contact | Switch-on temperature (NO) Contact | Switch-off temperature (NO) Contact |
01163.0-00 | +59°F / +15°C (± 9°F / 5K tolerance) | +41°F / +5°C (± 9°F / 5K tolerance) | +122°F / +50°C (± 11°F / 6K tolerance) | +104°F / +40°C (± 12.6°F / 7K tolerance) |
01163.0-01 | +77°F / +25°C (± 9°F / 5K tolerance) | +59°F / +15°C (± 9°F / 5K tolerance) | +140°F / +60°C (± 11°F / 6K tolerance) | +122°F / +50°C (± 12.6°F / 7K tolerance) |
01163.0-02 | +59°F / +15°C (± 9°F / 5K tolerance) | +41°F / +5°C (± 9°F / 5K tolerance) | +95°F / +35°C (± 11°F / 6K tolerance) | +77°F / +25°C (± 12.6°F / 7K tolerance) |
01163.0-03 | +77°F / +25°C (± 9°F / 5K tolerance) | +59°F / +15°C (± 9°F / 5K tolerance) | +122°F / +50°C (± 11°F / 6K tolerance) | +104°F / +40°C (± 12.6°F / 7K tolerance) |
Part No. | Switch-on temperature (NO) Contact | Switch-off temperature (NO) Contact | Switch-on temperature (NO) Contact | Switch-off temperature (NO) Contact |
01164.0-00 | +122°F / +50°C (± 11°F / 6K tolerance) | +104°F / +40°C (± 12.6°F / 7K tolerance) | +140°F / +60°C (±11°F / 6K tolerance) | +122°F / +50°C (± 12.6°F / 7K tolerance) |